12 position sampling (on-the-fly measurement), Position sampling (on−the−fly measurement), 12 position sampling (on−the−fly measurement) – Festo Контроллеры двигателя SFC-LAC User Manual

Page 191

Advertising
background image

5. Commissioning

5−87

Festo GDCP−SFC−LACI−DN−EN en 0812NH

5.6.12 Position sampling (on−the−fly measurement)

A local digital input (IN1 or IN2) not occupied by the
reference or limit switch can be used as a fast sample input.
With a falling (depending on configuration: a rising) edge at
the configured sample input, the current position value is
written (in 204A/05h or 06h) into a tab of the SFC−LACI and
can afterwards be read out by the higher−level control system
(PLC/IPC) (PNU 350 or PNU 351).

Overview of parameters for position sampling (on−the−fly measurement)

Parameter / Description

PNU

FCT

CI

Input that is going to be used for the position sampling:
value = 0: none
value = 1: IN1
value = 2: IN2

1305

x

6510/16h

Trigger mode
Ĉ Value = 1: cyclic" (continuous) = record position for every rising

(depending on configuration: and/or falling) edge

Ĉ Value = 2: single" (one−time) = record position only for the first rising

(depending on configuration: and/or falling) edge

352

x

204A/01h

Edge status
Ĉ Value = 0: An edge was not registered.

Writing 0 resets both edge events to 0.

Ĉ Value = 1: A falling edge has occurred and a new position value

was stored.

Ĉ Value = 2: A rising edge has occurred and a new position value

was stored.

Ĉ Value = 3: A rising and a falling edge have occurred, the respective

position values were stored.

353

ć

204A/02h

Advertising