Festo Контроллеры двигателя SFC-LAC User Manual
Page 272
Advertising
B. Parametrizing via field bus
B−52
Festo GDCP−SFC−LACI−DN−EN en 0812NH
DeviceNet Diagnosis
PNU
206
1 ... 6
Array
uint8
r
Description
Read out the field bus diagnostic data
Network Status 206
1
0x00:
Bus is inactive, missing bus power supply
0x01:
Serious error
0x04/5:
Error can be rectified (e.g. Timeout)
0x10:
Active connection with DeviceNet Master
0x20:
Device self test
0x40/50:
No connection to DeviceNet Master
Baudrate 206
2
Baud rate Values: 0 ... 2
Z 125, 250, 500 kBaud
0xFF
Z invalid baud rate
ć 206
3
(reserved)
MAC ID 206
4
Values: 0 ... 63 (0x00 ... 0x3F)
I/O Datalength 206
5
0x10:
8 bytes I/O data length (FHPP standard)
0x11:
16 bytes I/O data length (FHPP + FPC)
ć
206
6
(reserved)
CI
2FF4h
01h ... 06h
uint8
r
DeviceNet
C: 109
Aā: 1, 2, 4, 5
I: 1
uint8
r