6. Diagnosis and fault display

6−6

Festo GDCP−SFC−LACI−DN−EN en 0812NH

Bus status

I/F

Bus status

1)

ON

OFF

Off

The device is not online. The Dup_MAC_ID test is not yet
concluded. Possibly missing logic voltage.

ON

OFF

Flashes
green

2)

The Dup_MAC_ID test has been successfully concluded, and
the device is online. But the device is not yet assigned to a
master.

ON

OFF

Green

The device is online and assigned to a master

ON

OFF

Flashes
red

2)

For at least one I/O connection, the time was exceeded
(status Timed Out")

ON

OFF

Red

A critical error has occurred (duplicate MAC−ID or bus
switched off )

ON

OFF

Flashes
red and
green

3)

The device has ascertained a network access error and is in
the status Communication Failed". In addition, the device
received and answered a communication fault request
(Identify Communication Faulted Request ć Long Protocol").

1)

Display as per DeviceNet specification During start−up, the LED is switched off when valid bus
parameters are present; otherwise, there is a message in the control panel display.

2)

Flashing frequency 1 Hz

3)

Flashing frequency 2 Hz, i.e.Ăcolour changes every 250Ăms without going dark

Tab. 6/5:

I/F" LED