A.3 converting the units of measurement, Converting the units of measurement – Festo Контроллеры двигателя SFC-LAC User Manual
Page 220
A. Technical appendix
A−6
Festo GDCP−SFC−LACI−DN−EN en 0812NH
A.3
Converting the units of measurement
The CI interface works with increments [Inc, Inc/s, Inc/s
2
,
Inc/s
3
].
DNCE−...−LAS
The distance between two index lines (= north or south pole
of the magnetic displacement encoder) is
5 mm. The resolĆ
ution of the measurement system is 11 bits, which is the
same as 2048
d
(800
h
) increments. The increments are calcuĆ
lated by means of interpolation. This results in the following
conversions (all figures are decimal):
[Inc]
> [mm]
mm
+ xĄInc
2048ĄInc
5Ąmm
[mm]
> [Inc]
Inc
+ xĄmm
5Ąmm
2048ĄInc
DFME−...−LAS
The distance between two index lines (= north or south pole
of the magnetic displacement encoder) is
2 mm.
The resolution of the measurement system is 11 bits, which is
the same as 2048
d
(800
h
) increments. The increments are
calculated by means of interpolation. This results in the
following conversions (all figures are decimal):
[Inc]
> [mm]
mm
+ xĄInc
2048ĄInc
2Ąmm
[mm]
> [Inc]
Inc
+ xĄmm
2Ąmm
2048ĄInc