4 diagnostics via field bus, 1 overview, Diagnostics via field bus – Festo Контроллеры двигателя SFC-LAC User Manual

Page 210: Overview, 4 diagnostics via field bus 6.4.1 overview

Advertising
background image

6. Diagnosis and fault display

6−14

Festo GDCP−SFC−LACI−DN−EN en 0812NH

6.4

Diagnostics via field bus

6.4.1

Overview

ć

FHPP status bytes (see section 5.5.2)
ć SCON.B2 WARN ć Warning
ć SCON.B3 FAULT ć Fault
ć SPOS.B5 DEV

ć Drag error

ć SPOS.B6 STILL ć Standstill monitoring

ć

DeviceNet classes:

DeviceNet class

INST

1)

ATTR

PNU

2)

See...

101
(65h)

Diagnosis
memory

Diagnostic event

01h ... 10h

01h

200

Sections
6 4 2

(65h)

memory

Fault number

01h ... 10h

02h

201

6.4.2,
B.4.5

Time stamp

01h ... 10h

03h

202

102
(66h)

Diagnostic
memory
administration

Ĉ Record faults
Ĉ Resolution
Ĉ Clear buffer
Ĉ Number of entries

01h
01h
01h
01h

01h
02h
03h
04h

204

Section
B.4.5

108
(6Ch)

Current faults

Device faults

01h

01h

205

Section
B 4 5

(6Ch)

Warnings

01h

02h

215

B.4.5

Extended device faults

01h

0Ah

207

01h

0Bh

208

109
(6Dh)

Field bus
diagnosis

Ĉ Bus status
Ĉ Current baud rate
Ĉ Current MAC ID
Ĉ Current I/O data length

01h
01h
01h
01h

01h
02h
04h
05h

206

Section
B.4.5

1)

Access via Explicit Messaging

2)

Access via I/O Messaging (FHPP−FPC)

Tab. 6/7:

Diagnosis via field bus: DeviceNet classes