4. Control panel (only type SFC−LACI−...−H2)
4−10
Festo GDCP−SFC−LACI−DN−EN en 0812NH
[Diagnostic] [...]
Description
[DeviceNet Diag]
Bus diagnosis
Ĉ No Power /
BUSĂOff
No bus supply connected or the field bus was not
correctly parameterised. No connection to the master is
possible.
Ĉ Device
Operational
DeviceNet in the status Data exchange" and connected
to a master
Ĉ Device in
Standby
No connection with the DeviceNet master, device is ready
for operation
Ĉ Minor Fault
Recoverable fault has occurred (e.g. timeout)
Ĉ Unrecoverable
Fault
Serious fault detected (e.g. duplicated MAC ID); a reset
is needed to make the device ready for operation again.
Baudrate
Preset baud rate of the SFC−LACI
MAC ID
Address of the SFC−LACI
I/O Datalength
Set I/O data length.
Ĉ 8 bytes: only FHPP standard (the SFC−LACI is
controlled as per the Festo Handling and Positioning
Profile).
Ĉ 16 bytes: FHPP standard and FPC (additional use of
the FPC for parameterising the SFC−LACI)
[SW information]
SFC−LACI firmware version
Tab. 4/3:
[Diagnostic] menu