Determining pid constants (at, st, manual setup) – Rockwell Automation 900-TC32 Digital Temperature Controllers, Series B User Manual

Page 100

Advertising
background image

Publication 900-UM007D-EN-E - January 2011

3-30

Configuration & Basic Operation

Determining PID Constants
(AT, ST, Manual Setup)

AT (Auto-Tuning)

Figure 3.55

Overview

When you configure the controller to execute Auto-Tuning, the optimum PID
constants for the current set point during program execution are
automatically configured by the controller forcibly changing the manipulated
variable (MV) to calculate the characteristics (called the limit cycle method) of
the control target.

Either 40% AT or 100% AT can be selected depending on the width of MV
variation in the limit cycle. In the AT Execute/Cancel parameter, specify

at-2 (100% AT) or at-1 (40% AT). To cancel AT, specify off (AT cancel).

• Only 100% AT can be executed for heating and cooling control.
• AT cannot be executed when control has stopped or during ON/OFF
control.
• The results of AT are reflected in the Proportional Band (P), Integral Time
(I), and Derivative Time (D) parameters in the Adjustment function group.

The result of a controller AT cycle can be viewed/monitored from the
Proportional Band (P), Integral Time (I), and Derivative Time (D) parameters
in the Adjustment function group.

Figure 3.56 — PID

AT Description and Display Consideration

AT (Auto-Tuning) is started when you configure either

at-2 (100%) or

at-1 (40% AT).During execution of AT, the No. 1 display for the AT
Execute/Cancel parameter blinks (refer to Figure 3.57). When AT ends, the
AT Execute/Cancel parameter turns OFF, and the No. 1 display stops
blinking.

Figure 3.57 — AT Execute/Cancel Parameter

Adjustment Level

i

233

C

p

(0

d

40

Proportional
Band

Integral
Time

Derivative
Time

at

off

at

on

AT Execute/Cancel

No. 1 display

Advertising