Parameter Functions & Definitions

5-63

Note:

Calibration is NOT supported for the transfer output.

Related Parameter

• Transfer Output Upper-Limit, Transfer Output Lower-Limit (Initial

Setting function group, page 5-63)

Transfer Output Upper-Limit

Transfer Output Lower-Limit

Conditions of Use:

An analog current output must be assigned/configured.

The Transfer Output Type parameter must NOT be set to OFF.

Function:

This parameter allows you to configure the Upper- and

Lower-Limit values specifically for the transfer output and separate from the
actual function (e.g., Set Point Limits).

Table 5.BT — Transfer Output Destination

Control Output 1 Type

Control Output 2 Type

Transfer Output
Destination

Current Output

• No
• Relay Output
• Voltage Output (for driving SSR)

Control Output 1

• Relay Output
• Voltage output (for

driving SSR)

• No
• Relay Output
• Voltage Output (for driving SSR)

No

Table 5.BU

Transfer Output Type Selection

Default

OFF

off

off

Set point

sp

Set point during SP ramp

sp-m

PV

pv

MV monitor (heating)

mv

MV monitor (cooling)

c-mv

tr-h
tr-l