Publication 900-UM007D-EN-E - January 2011

4-58

Parameter Adjustments & Application Considerations

4. Select the Auto/Manual Select Addition parameter by pressing the M

key.

Figure 4.116

5. Use the U key to set the parameter to ON.

Figure 4.117

6. Press the O key for at least 1 second to move from the Advanced

Setting function group to the Initial Setting function group.

Figure 4.118

7. Press the O key for at least 1 second to move from the Initial Setting

function group to the Operation function group.

8. Select the Auto/Manual Switch parameter by pressing the M key.

Figure 4.119

9. Press the O key for at least 3 seconds to move from the Operation

function group to the Manual Control function group.

Figure 4.120

amad

off

Auto/manual
select addition

amad

on

in-t

5

Input type

a-m

Auto/manual
switch

C

25

0.0

PV/MV