In-t, Cntl, Alt1 – Rockwell Automation 900-TC32 Digital Temperature Controllers, Series B User Manual

Page 80: Al-1, Figure 3.8 — typical example 1

Advertising
background image

Publication 900-UM007D-EN-E - January 2011

3-10

Configuration & Basic Operation

Figure 3.8 — Typical Example 1

100

20

onof

pid

run
stop

25

0

C

in-t

5

cntl

onof

alt1

2

25

100

C

r-s

run

al-1

20

C

M

M

M

M

M

M

Input type:

5 (K thermocouple,

200

°

C to 1,300

°

C)

Control method: ON/OFF control
Alarm type:

2 (upper limit)

Alarm value 1: 20

°

C (deviation)

Set point:

100

°

C

Setup Procedure

Power ON

Initial Setting
function group

Set input
specifications

Set control
specifications

Set alarm type

Operation
function
group

Set alarm values

Start operation

Power ON

Operation
function
group

PV/SP

Press the

O

key for

at least 3 s.

Control stops.

Initial Setting
function group

Input type:

5

Check that
control method is
ON/OFF control.

ON/OFF
control:

PID

control:

Check alarm type.

Check input type.

Alarm 1 type:

2

Press the

O

key for

at least 1 s.

Control starts.

Operation
function group

Use the

U

and

D

keys to set the

SP to 100

°

C.

PV/SP:

Confirm that
control is running.

Running

Stopped:

Use the

U

and

D

keys to set the

alarm value to 20

°

C

.

Alarm value 1:

Start operation.