Publication 900-UM007D-EN-E - January 2011

Parameter Adjustments & Application Considerations

4-35

Initial Setting/Communications Protection

This portion of the Key Protect function group restricts movement by keypad
operation to the Initial Setting function group, Communications Setting
function group, and Advanced Setting function group (refer to Table 4.W).

Figure 4.59

Setting Change Protection

This portion of the Protect group protects controller setup from being
changed by operating the keys on the front panel.

Figure 4.60

• The all protect indication (

) will light when Setting Change Protect

is configured to ON.

Table 4.X

The all protect indication (

) will light when Setting Change protect

is configured.

Table 4.W — Initial Setting/Communications Protection

Set Value

Function Group

Initial Setting

Communications
Setting Advanced

Setting

0

Possible to reach Possible to reach

Possible to reach

1

Possible to reach Possible to reach

Not possible to reach

2

Not possible to
reach

Not possible to reach

Not possible to reach

➊Default

Configured Value

Description

OFF

Setup can be changed by key operation.

ON

Setup cannot be changed by key operation. (The
Protect function group can be changed.)

➊Default

icpt

1

wtpt

off