Alh2 alh3 tr-t, Alarm 2 hysteresis, Alarm 3 hysteresis – Rockwell Automation 900-TC32 Digital Temperature Controllers, Series B User Manual

Page 290

Advertising
background image

Publication 900-UM007D-EN-E - January 2011

5-62

Parameter Functions & Definitions

Alarm 2 Hysteresis

Conditions of Use:

Alarm 2 must be assigned. The alarm 2 type must NOT

be 0, 12, or 13.

Alarm 3 Hysteresis

Conditions of Use:

Alarm 3 must be assigned. The alarm 3 type must NOT

be 0, 12, or 13.

Function:

These parameters set the hysteresis (allowed deviation from the

configured alarm value) for alarms 1, 2, and 3.

Note:

Set

None as the unit for 0 to 50 millivolt.

Related Parameters

• Alarm value 1 to 3 (page 5-16), Alarm value upper limit 1 to 3 (page

5-18), Alarm value lower limit 1 to 3 (page 5-18) (Operation function
group)

• Alarm 1 to 3 type (Initial Setting function group, page 5-59)

Transfer Output Type (900-TC8, 900-TC16)

Conditions of Use:

An analog current output must be assigned/configured

Function:

This parameter allows you to configure the analog current output

for a specific type of transfer output. Refer to Table 5.BU.

Note:

If the analog current output is NOT used as a transfer output, configure
this parameter to OFF (default).

Table 5.BS

Controller Models

Configurable Range Units

Default

Model with thermocouple/resistance
thermometer universal input

0.1...999.9

°C or °F 0.2

Model with analog input

0.01...99.99

%FS

0.02

alh2

alh3

tr-t