Monitor Setting Item Function Group
The contents displayed vary depending on the Monitor/Setting Value 1 to 5
(Advanced Setting function group).

Table B.F — Advanced Setting Function Group

Parameters

Characters

Setting (Monitor) Value

Display

Default

Unit

Set Value

Parameter Initialization

init

OFF, FACT

off

fact

OFF

None

Multi-SP Use

mspu

OFF, ON

off on

OFF

None

SP Ramp Time Unit

spru

S:

EU/second

M:

EU/minute

s m

M

None

Standby Sequence
Reset

rest

Condition A, condition B

a b

Condition A

None

HB ON/OFF

hbu

OFF, ON

off on

ON

None

Auxiliary Output 1
Open in Alarm

al1n

N-O:

Open in alarm

N-C:

Close in alarm

n-o

n-c

N-O

None

Auxiliary Output 2
Open in Alarm

al2n

N-O:

Open in alarm

N-C:

Close in alarm

n-o

n-c

N-O

None

Auxiliary Output 3
Open in Alarm

al3n

N-O:

Open in alarm

N-C:

Close in alarm

n-o

n-c

N-O

None

Heater Burnout Latch

hbl

OFF, ON

off on

OFF

None

Heater Burnout
Hysteresis

hbh

0.1…50.0

0.1

A

ST Stable Range

st-b

0.1…999.9

15.0

°C or °F

α

alfa

0.00…1.00

0.65

None

AT Calculated Gain

at-g

0.1...10.0

0.8

None

AT Hysteresis

at-h

Universal input: 0.1...999.9

0.8

°C or °F

Analog input: 0.01...999.9

0.20

%FS

Limit Cycle MV
Amplitude

lcma

5.0...50.0

20.0

%

Input Digital Filter

inf

0.0…999.9

0.0

Second

Additional PV Display

pvad

OFF, ON

off on

OFF

None

MV Display

o-dp

OFF, ON

off on

OFF

None

Automatic Display
Return Time

ret

OFF or 1…99

off

1 to 99

OFF

Second

Alarm 1 Latch

a1lt

OFF, ON

off on

OFF

None

Alarm 2 Latch

a2lt

OFF, ON

off on

OFF

None

Alarm 3 Latch

a3lt

OFF, ON

off on

OFF

None

Move to Protect
function group Time

prlt

1…30

3

Second

Input Error Output

sero

OFF, ON

off on

OFF

None