Init, A1on, A1of – Rockwell Automation 900-TC32 Digital Temperature Controllers, Series B User Manual
Page 182: In-t
Advertising

Publication 900-UM007D-EN-E - January 2011
4-46
Parameter Adjustments & Application Considerations
3. Press the D key to enter the password (−169) and move from the Initial
Setting function group to the Advanced Setting function group.
Figure 4.87
4. Press the M key to select the Alarm 1 ON Delay parameter.
Figure 4.88
5. Press the U key to set the parameter to 5.
Figure 4.89
6. Press the M key to select the Alarm 1 OFF Delay parameter.
Figure 4.90
7. Press the U key to set the parameter to 10.
Figure 4.91
8. Press the O key for at least 1 second to move from the Advanced
Setting function group to the Initial Setting function group.
Figure 4.92
init
off
Parameter
initialization
a1on
0
Alarm 1 ON
delay
a1on
5
a1of
0
Alarm 1 OFF
delay
a1of
10
in-t
5
Input type