Init, A1on, A1of – Rockwell Automation 900-TC32 Digital Temperature Controllers, Series B User Manual

Page 182: In-t

Advertising
background image

Publication 900-UM007D-EN-E - January 2011

4-46

Parameter Adjustments & Application Considerations

3. Press the D key to enter the password (−169) and move from the Initial

Setting function group to the Advanced Setting function group.

Figure 4.87

4. Press the M key to select the Alarm 1 ON Delay parameter.

Figure 4.88

5. Press the U key to set the parameter to 5.

Figure 4.89

6. Press the M key to select the Alarm 1 OFF Delay parameter.

Figure 4.90

7. Press the U key to set the parameter to 10.

Figure 4.91

8. Press the O key for at least 1 second to move from the Advanced

Setting function group to the Initial Setting function group.

Figure 4.92

init

off

Parameter
initialization

a1on

0

Alarm 1 ON
delay

a1on

5

a1of

0

Alarm 1 OFF
delay

a1of

10

in-t

5

Input type