Application examples – Rockwell Automation 900-TC32 Digital Temperature Controllers, Series B User Manual

Page 121

Advertising
background image

Publication 900-UM007D-EN-E - January 2011

Configuration & Basic Operation

3-51

• The allowable controller heater current range is 0.1…49.9 A. Heater

burnout, HS, and heater overcurrent are not detected when the
configured alarm value is 0.0 or 50.0.
When the configured alarm value is 0.0, the Heater Burnout Alarm is
always OFF, the HS, and HO Alarm is always ON.
When the configured alarm value is 50.0, the Heater Burnout Alarm is
always ON, and the HS Alarm is always OFF, and the HOA is always
OFF.

• Configure the total current value for normal heater operation to 50 A or

less. When a current value of 55.0 A is exceeded,

ffff is displayed in

the Heater Current 1 (and 2) Value Monitor and Leakage Current 1 (and
2) Monitor parameters.

Application Examples

Single-Phase Heaters

EXAMPLE

Using a 200V AC, 1 kW Heater

The heater power supply provides 5 A when the current is normal, and 0 A
when there is a burnout.

Figure 3.99

Therefore, the heater burnout detection current is calculated as follows:

CT

0 A

200 V

CT

5 A

5 A

200 V

Normal

AC line

Load

Load

AC line

To CT Controller input

To CT Controller input

Burnout

Load (such as a heater)

Burnout

Heater burnout

detection current =

(Normal current) + (Heater burnout current)

2

=

5 + 0

2

= 2.5 [A]

Advertising