Setting Heater Burnout Detection

1.

Press the

O

key for at least 1 second to move from the Advanced

Setting function group to the Initial Setting function group and then to
the Operation function group.

Figure 3.111

2.

Press the

O

key for less than 1 second to move from the Operation

function group to the Adjustment function group.

Figure 3.112

3.

Select the Heater Current 1 Value Monitor parameter by pressing the

M

key. Check the current value. Next, set the Heater Burnout Detection 1
parameter.

Figure 3.113

4.

Select the Heater Burnout Detection 1 parameter by pressing the

M

key. Refer to How to Calculate Heater Current Detection Values when
making the settings.

Figure 3.114

5.

For this example, set 2.5. To return to the Operation function group,
press the

O

key for less than 1 second.

Figure 3.115

C

25

100

PV/SP

l.adj

Adjustment
function
group display

ct1

0.0

Heater current
1 value monitor

hb1

0.0

Heater burnout
detection 1

hb1

2.5