Rockwell Automation 900-TC32 Digital Temperature Controllers, Series B User Manual
Page 362

Publication 900-UM007D-EN-E - January 2011
B-2
Table B.B — Adjustment Function Group
Parameters
Characters
Setting (Monitor) Value
Display
Default
Unit
Set Value
Adjustment Level Display
l.adj
AT Execute/Cancel
at
OFF, AT Cancel AT-2: 100%
AT Execute AT-1: 40% AT
Execute
off
at-2
at-1
OFF
None
Communications Writing
cmwt
OFF, ON
off on
OFF
None
Heater Current 1 Value Monitor
ct1
0.0…55.0
A
Heater Overcurrent Detection 1
oc1
0.0…50.0
50.0
A
Heater Current 2 Value Monitor
ct2
0.0…55.0
A
Heater Overcurrent Detection 2
oc2
0.0…50.0
50.0
A
Leakage Current 1 Monitor
lcr1
0.0…55.0
A
HS Alarm 1
hs1
0.0…50.0
50.0
A
Leakage Current 2 Monitor
lcr2
0.0…55.0
A
HS Alarm 2
hs2
0.0…50.0
50.0
A
Heater Burnout Detection 1
hb1
0.0…50.0
0.0
A
Heater Burnout Detection 2
hb2
0.0…50.0
0.0
A
SP 0
sp-0
SP Lower-Limit to SP
Upper-Limit
0
EU
SP 1
sp-1
SP Lower-Limit to SP
Upper-Limit
0
EU
SP 2
sp-2
SP Lower-Limit to SP
Upper-Limit
0
EU
SP 3
sp-3
SP Lower-Limit to SP
Upper-Limit
0
EU
Temperature Input Shift
ins
−199.9…999.9
0.0
°C or °F
Upper-Limit Temperature Input
Shift Value
insh
−199.9…999.9
0.0
°C or °F
Lower-Limit Temperature Input
Shift Value
insl
−199.9…999.9
0.0
°C or °F
Proportional Band
p
Universal input:
0.1…999.9
8.0
°C or °F ➊
Analog input: 0.1…999.9
10.0
%FS
Integral Time
i
0…3,999
233
Second
Derivative Time
d
RT OFF: 0…3,999
40
Second
RT ON: 0.0…999.9
40.0
Second
Cooling Coefficient
c-sc
0.01…99.99
1.00
None