Parameter Adjustments & Application Considerations

4-27

Application Considerations

If a change is made to the set point upper and/or lower-limit value with
the current set point outside the limiter range, the set point is forcibly
changed by the controller to the sensor’s upper SP limit or lower SP
limit value, whichever is closer.

When the Input Type or temperature units are changed, the set point
limiter is forcibly reset to that of the new sensor setting range.

Set Point Limit Setup

To configure the Set Point Upper- and Lower-Limit parameters, you must
be in the Initial Setting function group. This example describes how to
configure the set point limiter when using a type K thermocouple (normal
full range: –200…1300

°C).

Figure 4.41

EXAMPLE

Operation Procedure: Configuring the Set Point Upper-Limit

Configure the Set Point Upper-Limit Value to 1000

1. Press the

key for at least 3 seconds to move from the Operation

function group to the Initial Setting function group.

Table 4.T — Parameters

Symbol

Parameters: Function group

Description

sl-h

Set Point Upper-Limit: Initial Setting function
group

For limiting the SP
setting

sl-l

Set Point Lower-Limit: Initial Setting function
group

Set point limitter range

Normal/Full Sensor range (Type K thermocouple)

-200

1300

1000

-100