Parameter Adjustments & Application Considerations
4-67
Program Pattern
Either of two program patterns (STOP or Continue) can be selected. The
simple program operation will not be performed if the Program Pattern
parameter is configured to OFF.
Pattern 1 (STOP)
Control will stop and the STOP control mode will be entered when the simple
program has ended.
Figure 4.147
Pattern 2 (CONT)
Control will continue in RUN control mode when the simple program has
ended.
Figure 4.148
RSET
→
STRT
PV
Set point
Wait band
Wait band
Soak time
END display
END output
Automatically switches
from RUN to STOP control
mode.
RSET
→
STRT
PV
Set point
Wait band
Wait band
Soak time
END display
END output
RUN mode continues.