Publication 900-UM007D-EN-E - January 2011

Calibration

C-9

10. Change the wiring as follows

Figure C.13

Disconnect the STV to enable the thermocouple of the cold junction
compensator. When doing this, be sure to disconnect the wiring on the STV
side.

11. Allow the count value on the No. 2 display to fully stabilize, then press

the

D Key to temporarily register the calibration settings.

Figure C.14

12. When the M Key is pressed, the status changes as shown to the left.

The data to be temporarily registered is not displayed if it is not
complete. Press the

U Key. The No. 2 display changes to yes. Release

the key and wait two seconds or press the

M Key. This stores the

temporarily registered calibration data to EEPROM. To cancel the
saving of temporarily registered calibration data to EEPROM, press the

M Key (while no is displayed in the No. 2 display) without pressing the

U Key.

13. The calibration mode is ended by turning the power OFF

14. Allow the count value on the No. 2 display to fully stabilize, then press

the

D key to temporarily register the calibration setup.

Short-Circuit

Zero

Controller

STV

DMM

+

OUTPUT

INPUT

Compensating conductor of currently
selected thermocouple.
Use the K thermocouple compensating
conductor for:

• E, R, S, B, W, and PLII thermocouples and
• an infrared temperature sensor

Open in Non-connected State