Publication 900-UM007D-EN-E - January 2011

4-26

Parameter Adjustments & Application Considerations

Parameters

Configuring the SP Upper-
and Lower-Limit Values

Set Point Limiter

The maximum allowable configuration range of the set point is limited by the
set point limiter parameter. The set point limiter is used to prevent someone
from configuring the set point to some value outside the maximum range
called for by the application, thereby preventing the control target from
reaching an abnormal temperature. The upper- and lower-limit values of the
set point limiter are configured from the Set Point Upper-Limit and Set Point
Lower-Limit parameters in the Initial Setting function group, respectively.

Figure 4.40

Table 4.S

Symbol

Parameter: Level

Description

eV-1

Event Input Assignment 1: Initial
Setting function group

Function of event input function

eV-2

Event Input Assignment 2: Initial
Setting function group

eV-m

Number of Multi-SP Uses: Initial
Setting function group

B

(setting possible)

Setting range

Changed to upper
limit value

Input type changed

Sensor range

Set point limitter

Changed to the
new upper limit
value

Set point

B

A

C

Set point

Set point

Sensor upper- and lower-limit values

Set point

Upper- and lower-limit values of the limitter

x

(setting not possible)

x