Configuring the sp upper- and lower-limit values, Parameters, Set point limiter – Rockwell Automation 900-TC32 Digital Temperature Controllers, Series B User Manual
Page 162

Publication 900-UM007D-EN-E - January 2011
4-26
Parameter Adjustments & Application Considerations
Parameters
Configuring the SP Upper-
and Lower-Limit Values
Set Point Limiter
The maximum allowable configuration range of the set point is limited by the
set point limiter parameter. The set point limiter is used to prevent someone
from configuring the set point to some value outside the maximum range
called for by the application, thereby preventing the control target from
reaching an abnormal temperature. The upper- and lower-limit values of the
set point limiter are configured from the Set Point Upper-Limit and Set Point
Lower-Limit parameters in the Initial Setting function group, respectively.
Figure 4.40
Table 4.S
Symbol
Parameter: Level
Description
eV-1
Event Input Assignment 1: Initial
Setting function group
Function of event input function
eV-2
Event Input Assignment 2: Initial
Setting function group
eV-m
Number of Multi-SP Uses: Initial
Setting function group
B
(setting possible)
Setting range
Changed to upper
limit value
Input type changed
Sensor range
Set point limitter
Changed to the
new upper limit
value
Set point
B
A
C
Set point
Set point
Sensor upper- and lower-limit values
Set point
Upper- and lower-limit values of the limitter
x
(setting not possible)
x