Rockwell Automation 900-TC32 Digital Temperature Controllers, Series B User Manual

Page 374

Advertising
background image

Publication 900-UM007D-EN-E - January 2011

B-14

➊ Set “None” as the unit for analog inputs (23: 0 to 50 mV).

➋ The setting range depends on whether control output 1 is a current output or voltage output (for driving SSR).

➌ P.END (program end output) can be configured even when the program pattern is configured to OFF, but the
function will be disabled.
➍ Turns ON when either the control output 1 or 2 ON/OFF count alarm is ON.

Control Output 2 ON/
OFF Count Alarm Set
Value

ra2

0....9999

0

100 times

ON/OFF Counter Reset

rac

0: Disable the counter reset

function.

1: Reset the control output 1

ON/OFF counter.

2: Reset the control output 2
ON/OFF counter.

o

None

Move to Calibration
function group

cmov

−1999…9,999

0

None

Table B.F — Advanced Setting Function Group

Parameters

Characters

Setting (Monitor) Value

Display

Default

Unit

Set Value

Table B.G — Protect Function Group

Parameters

Characters

Setting (Monitor) Value

Display

Default

Unit

Set value

Move to Protect function
group

pmov

−1999…9,999

0

None

Operation/Adjustment
Protect

oapt

0…3

0

None

Initial
Setting/Communications
Protect

icpt

0…2

1

None

Setting Change Protect

wtpt

OFF, ON

off on

OFF

None

PF Key Protect

pfpt

OFF, ON

off on

OFF

None

Parameter Mask Enable

pmsk

OFF, ON

off on

ON

None

Password to Move to
Protect function group

prlp

−1999…9,999

0

None

Table B.H Communications Function Group

Parameters

Characters

Setting (monitor) value

Display

Default

Unit

Set value

Protocol Setting

psel

900-TC, Modbus

cwf

mod

900-TC

None

Communications Unit
No.

u-no

0…99

1

None

Communications Baud
Rate

bps

1.2, 2.4, 4.8, 9.6, 19.2, 38.4, or
57.6

1.2 2.4

4.8 9.6

19.2 38.4

57.6

9.6

kbps

Communications Data
Length

len

7, 8

7

Bit