Soak, Soak time – Rockwell Automation 900-TC32 Digital Temperature Controllers, Series B User Manual

Page 267

Advertising
background image

Publication 900-UM007D-EN-E - January 2011

Parameter Functions & Definitions

5-39

Related Parameters

• PID ON/OFF, Standard or Heating/Cooling (Initial Setting function

group, page 5-55)

Soak Time

Conditions of Use:

The Program Pattern parameter must NOT be set to

OFF.

Function:

This parameter enables you to configure the soak or delay time for

the control operation when using the simple program function.

Related Parameters

• Program Start, Soak Time Remain (Operation function group, page

5-15)

• Wait Band (Adjustment function group, page 5-40)
• Program Pattern (Initial Setting function group, page 5-57)
• Soak Time Unit (Advanced Setting function group, page 5-96)

Table 5.AQ

Parameters

Controller Type

Configurable
Range

Units

Default

Hysteresis (heating)

With Thermocouple or Resistance Thermometer (RTD)

0.1…999.9

°C or °F ➊

1.0

With Analog Inputs

0.01…99.99

%FS

0.10

Hysteresis (cooling)

With Thermocouple or Resistance Thermometer (RTD)

0.0…999.9

°C or °F ➊

1.0

With Analog Inputs

0.01…99.99

%FS

0.10

➊ Set NONE as the unit for Controllers with 0…50 Millivolt Inputs.

Table 5.AR

Configurable Range

Units

Default

1…9999

Minutes or hours

1

soak