Soak, Soak time – Rockwell Automation 900-TC32 Digital Temperature Controllers, Series B User Manual
Page 267

Publication 900-UM007D-EN-E - January 2011
Parameter Functions & Definitions
5-39
Related Parameters
• PID ON/OFF, Standard or Heating/Cooling (Initial Setting function
group, page 5-55)
Soak Time
Conditions of Use:
The Program Pattern parameter must NOT be set to
OFF.
Function:
This parameter enables you to configure the soak or delay time for
the control operation when using the simple program function.
Related Parameters
• Program Start, Soak Time Remain (Operation function group, page
5-15)
• Wait Band (Adjustment function group, page 5-40)
• Program Pattern (Initial Setting function group, page 5-57)
• Soak Time Unit (Advanced Setting function group, page 5-96)
Table 5.AQ
Parameters
Controller Type
Configurable
Range
Units
Default
Hysteresis (heating)
With Thermocouple or Resistance Thermometer (RTD)
0.1…999.9
°C or °F ➊
1.0
With Analog Inputs
0.01…99.99
%FS
0.10
Hysteresis (cooling)
With Thermocouple or Resistance Thermometer (RTD)
0.0…999.9
°C or °F ➊
1.0
With Analog Inputs
0.01…99.99
%FS
0.10
➊ Set NONE as the unit for Controllers with 0…50 Millivolt Inputs.
Table 5.AR
Configurable Range
Units
Default
1…9999
Minutes or hours
1
soak