Parameter Adjustments & Application Considerations

4-7

EXAMPLE

In this example, we use the non-contact (infrared) sensor
type K thermocouple 0…260

°C specification to do a

2-point shift.

YL and YH in equations 1 and 2 are set temperature
Lower-Limit (YL = 0

°C) and set temperature Upper-Limit

(YH = 260

°C). Check the temperature of the control

target.

When the room temperature (X1) is 25

°C, the readout on

the controller (Y1) is 40

°C, and when the temperature near

the set point (X2) is 110

°C, the readout on the controller

(Y2) becomes 105

°C.

Lower-limit temperature input shift value:

Upper-limit temperature input shift value:

C

insl

-27.3

Lower-limit
temperature
input shift
value

x {(110 – 105) – (25 – 40)} + (25 – 40) = –27.3

°

C

0 – 40

105 – 40

insl

=

C

insh

52.7

Upper-limit
temperature
input shift
value

insh

=

x {(110 – 105) – (25 – 40)} + (25 – 40) = –52.7

°

C

60 – 40

105 – 40