Parameter Adjustments & Application Considerations

4-25

Switching 40% ATExecute/Cancel

When AT-1 (40% AT Execute/Cancel) is set for either the Event Input
Assignment1 or Event Input Assignment 2 parameter, 40% AT will be
executed when event input 1 or 2 turns ON and will be cancelled when the
input turns OFF

Switching Setting Change Enable/Disable

When WTPT (Setting Change Enable/Disable) is set for either the Event
Input Assignment 1 or Event Input Assignment 2 parameter, the setting
change will be disabled when event input 1 or 2 turns ON and will be enabled
when the input turns OFF.

Switching Alarm Latch Cancel

When LAT (Alarm Latch Cancel) is set for either the Event Input Assignment
1or Event Input Assignment 2 parameter, all alarm latches (alarms 1 to 3,
heater burnout, HS alarm, and heater over-current latch) will be cancelled
when event input 1 or 2 turns ON.

Table 4.P

Setting

Input

Status

Event Input 1 or 2

OFF

40% AT cancelled

Event Input 1 or 2

ON

40% AT executed

Table 4.Q

Setting

Input Contact

Status

Event input 1 or 2

OFF

Enabled

Event input 1 or 2

ON

Disabled

Table 4.R

Setting

Input Contact

Status

Event input 1 or 2

OFF

---

Event input 1 or 2

ON

Cancelled