Publication 900-UM007D-EN-E - January 2011

4-20

Parameter Adjustments & Application Considerations

The following table shows the relationship between the Multi-SP Uses
parameter value and the selected set point.

Note: The set point can also be switched using PC communications. This is

supported by 900-TC8, 900-TC16, and 900-TC32.

Multi-SP Setup

EXAMPLE

Operation Procedure: To Select Set Points (0/1/2/3)

The following example configures the Number of Multi-SP Uses parameter to
2 (Multi-SP, 4 points). Refer to Table 4.I.

Before you configure the Number of Multi-SP Uses parameter, you must first
cancel protection from the Advanced Setting function group. For additional
details on how to cancel key protection, refer to page 4-33, Using the Key Protect
Function Group

.

1. Press the

key for at least 3 seconds to move from the Operation

function group to the Initial Setting function group.

Figure 4.33

Table 4.I

Multi-SP Uses Parameter Value

Selected Set Point

0

Select Set Point 0 value

1

Select Set Point 1 value

2

Select Set Point 2 value

3

Select Set Point 3 value

C

25

100

PV/SP