Rockwell Automation 900-TC32 Digital Temperature Controllers, Series B User Manual

Page 19

Advertising
background image

Publication 900-UM007C-EN-E - January 2011

Preface

P-v

Body Removal

900-TC8, 900-TC16, &
900-TC32 Ratings

Table P.D — Body Removal

Series A

Series B

900-TC8

• Removal using screws

• Removal using hooks

900-TC16 ---

• No change for body removal

900-TC32 ---

• No change for body removal

Table P.E — 900-TC8, 900-TC16, & 900-TC32 Ratings

Series A

Series B

Input sensor types for thermocouple inputs

---

The following types of thermocouple input
were added: W and PLII.

Input range for E thermocouple: 0...600 ºC

Input range increased for E thermocouple:
-200...600 ºC

Input accuracy

• Thermocouple: ±0.5% PV or ±1ºC,

whichever is greater) ±1 digit

• Platinum resistance thermometer:

(±0.5%PV or ±1ºC, whichever is
greater) ± 1 digit

• Analog input: ±0.5% FS ± digit

• Thermocouple: ±0.3% PV or ±1ºC,

whichever is greater) ±1 digit

• Platinum resistance thermometer:

(±0.2%PV or ±.08ºC, whichever is
greater) ± 1 digit

• Analog input: ±0.2% FS ± digit