Counting control output on/off operations, Control output on/off count function – Rockwell Automation 900-TC32 Digital Temperature Controllers, Series B User Manual

Page 223

Advertising
background image

Publication 900-UM007D-EN-E - January 2011

Parameter Adjustments & Application Considerations

4-87

Counting Control Output
ON/OFF Operations

Control Output ON/OFF Count Function

With Control Output 1 and 2 ON/OFF outputs (relay outputs or voltage
outputs for driving SSR), the number of times that a control output turns ON
and OFF can be counted. Based on the control output ON/OFF count alarm
configured value, an alarm can be output and an error can be displayed if the
configured count value is exceeded.

The default configuration of the Control Output ON/OFF Alarm Setting
parameter is 0. ON/OFF operations are not counted when this parameter is
configured to 0. To enable counting ON/OFF operations, change the
configuration to a value other than 0.

Control Output ON/OFF Counter Monitor Function

This function is not displayed when the Control Output 1 ON/OFF Alarm
Setting and the Control Output 2 ON/OFF Alarm Setting parameter are set
to 0, or when the control outputs are set for linear (analog) outputs.

Display When ON/OFF Count Alarm Occurs

When an ON/OFF count alarm occurs, the PV display in the No. 1 display
shown below alternates with the

ralm display on the No. 2 display.

• PV
• PV/SP (Including the items displayed by setting the “PV/SP” Display
Screen Selection parameter.)
• PV/Manual MV, PV/SP/Manual MV
• PV/SP displayed for the monitor/setting items

Control Output ON/OFF Count Alarm Function

If the ON/OFF counter exceeds the control output ON/OFF count alarm
configured value, an ON/OFF count alarm will occur. The alarm status can be
assigned to a control output or an auxiliary output, or it can be displayed at the

Table 4.AN

Parameter Name

Configurable Range Unit

Default

Control Output 1 ON/OFF Count
Monitor

0 to 9999

100 times 0

Control Output 2 ON/OFF Count
Monitor (900-TC8 & 900-TC16)

0 to 9999

100 times 0

PV/SP

25

100

25

ralm

100

C

C

Normal

ON/OFF Count Alarm

Alternating
display