The heater burnout current when there is a burnout at the load is as follows:
(heater burnout detection current) = (17.3 + 10) / 2

≈ 13.65 [A]

To enable detection in either case, use 16.1 A as the heater burnout detection
current.

Figure 3.102 — Heater Burnout Detection

EXAMPLE

Using Three 200V AC, 2 kW Heaters, Star Connecting Lines

The current when each phase is normal is 5.8 A (

≈ 10 A × (1 /√3)).

Figure 3.103 — Star Connecting Lines

The heater burnout detection current for this connecting line is
5.4 A (= (5.8 + 5) / 2).

CT

CT

Load

Load

200 V

200 V

15 A

15 A

200 V

CT

CT

Load

Load

200 V

200 V

10 A

17.3 A

10 A

200 V

Burnout

Burnout

Burnout

Load

Load

To CT input

To CT input

Current when there is a burnout = 10 A

Ч

3

Ч

(

3/2) = 15 A

Current when there is a burnout = 10 A

Ч

3

Ч

(1/

3) = 10 A

Burnout

To CT Controller input

To CT Controller input

CT

CT

200 V

200 V

5.8 A

5.8 A

5.8 A

200 V

Load

Load

Load

Normal

To CT input

Load (such as a heater)

To CT Controller input