Using three 200v ac, 1 kw heaters, Using three-phase heaters, delta connecting lines – Rockwell Automation 900-TC32 Digital Temperature Controllers, Series B User Manual

Page 122

Advertising
background image

Publication 900-UM007D-EN-E - January 2011

3-52

Configuration & Basic Operation

EXAMPLE

Using Three 200V AC, 1 kW Heaters

The heater power supply provides 15 A when the current is normal, and 10 A
when there is a burnout.

Figure 3.100 — Using Three 200V AZ, 1 kW Heaters

Therefore, the heater burnout detection current is calculated as follows:

EXAMPLE

Using Three-Phase Heaters, Delta Connecting Lines

The current when each phase is normal is 17.3 A (

≈ √3 × 10 A).

Figure 3.101 — Delta Connecting Lines

The heater burnout current when there is a burnout at the load line is as
follows: (heater burnout detection current) = (17.3 + 15) / 2

≈ 16.1 [A]

10 A

10 A

CT

15 A

15 A

200 V

CT

200 V

Normal

To CT Controller input

To CT Controller input

Burnout

Load

Load

Load

Load

Load

Load

Burn-
out

Heater burnout

detection current =

(Normal current) + (Heater burnout current)

2

=

15 + 10

2

= 12.5 [A]

CT

Load

Load

200 V

200 V

17.3 A

17.3 A

17.3 A

200 V

Normal

To CT input

Load

To CT Controller input