Mv at pv error – Rockwell Automation 900-TC32 Digital Temperature Controllers, Series B User Manual

Page 212

Advertising
background image

Publication 900-UM007D-EN-E - January 2011

4-76

Parameter Adjustments & Application Considerations

Note: The order of priority is as follows: Manual MV > MV at stop > MV at

PV error.

MV at PV Error

You can configure the amount the MV is output during an input error
condition. The MV at stop takes priority when stopped and the manual MV
takes priority in manual mode.

Note: The order of priority is as follows: Manual MV > MV at stop > MV at

PV error.

The order of priority of the MVs is illustrated in the following diagram.

Figure 4.166

Table 4.AH

Parameter Configurable Range

Unit

Default

MV at Stop

−5.0…105.0 for standard control

−105.0…105.0 (heating/cooling control)

%

0.00

Table 4.AI

Parameter

Configurable Range

Unit

Default

MV at PV error

−5.0…105.0 for standard control

−105.0…105.0 (heating/cooling control)

%

0.0

PID
calculations

MV upper limit

Manipulated variable

Time

MV lower limit

MV at PV Error

Input error

RUN/STOP

MV at Stop

Manual MV

Auto/manual switch

Output