Mv at pv error – Rockwell Automation 900-TC32 Digital Temperature Controllers, Series B User Manual
Page 212

Publication 900-UM007D-EN-E - January 2011
4-76
Parameter Adjustments & Application Considerations
Note: The order of priority is as follows: Manual MV > MV at stop > MV at
PV error.
MV at PV Error
You can configure the amount the MV is output during an input error
condition. The MV at stop takes priority when stopped and the manual MV
takes priority in manual mode.
Note: The order of priority is as follows: Manual MV > MV at stop > MV at
PV error.
The order of priority of the MVs is illustrated in the following diagram.
Figure 4.166
Table 4.AH
Parameter Configurable Range
Unit
Default
MV at Stop
−5.0…105.0 for standard control
−105.0…105.0 (heating/cooling control)
%
0.00
Table 4.AI
Parameter
Configurable Range
Unit
Default
MV at PV error
−5.0…105.0 for standard control
−105.0…105.0 (heating/cooling control)
%
0.0
PID
calculations
MV upper limit
Manipulated variable
Time
MV lower limit
MV at PV Error
Input error
RUN/STOP
MV at Stop
Manual MV
Auto/manual switch
Output
1