Publication 900-UM007D-EN-E - January 2011

Calibration

C-17

Figure C.33

6. When the M key is pressed, the status changes as shown in the figure

below.
Set the STV to 1V.

Allow the count value on the No. 2 display to fully stabilize, then press
the

D key to temporarily register the calibration settings.

If this count value is outside of the specified range, the No. 2 display will
flash and the count value will not be temporarily registered.

Figure C.34

7. When the M key is pressed, the status changes as shown in the figure

below.
The data to be temporarily registered is not displayed if it is not
complete.
Press the

U key. The No. 2 display changes to yes. Release the key and

wait 2 seconds or press the

M key. This stores the temporarily

registered calibration data to EEPROM.
To cancel the saving of temporarily registered calibration data to
EEPROM, press the

M key (while no is displayed in the No. 2 display)

without pressing the

U key.

Figure C.35

8. The calibration mode is ended by turning the power OFF.

1v

-

5

c7c3

Input Type

2 or 3:

2v10

b104

Input Type 4:

1v

-

1

5ac0

Input Type

2 or 3:

2v

-

1

4ad9

Input Type

4:

str

no