O1-t – Rockwell Automation 900-TC32 Digital Temperature Controllers, Series B User Manual
Page 292

Publication 900-UM007D-EN-E - January 2011
5-64
Parameter Functions & Definitions
Related Parameter
• Transfer Output Type (Initial Setting function group, page 5-62)
Linear Current Output (900-TC8, 900-TC16)
Conditions of Use:
Control output 1 must be an analog current output.
Function:
This parameter allows you to configure the output type for the
linear analog current outputs and select either 4…20 mA or 0…20 mA.
Note:
Even when control output 1 is used as a control output or transfer
output the 0 to 20 mA selection can be used.
Related Parameter
• Transfer Output Type (Initial Setting function group, page 5-62)
Table 5.BV
Transfer
Output Type
Configurable Range
Default Transfer Output
Units
Lower-Limit
Upper-Limit
Set Point
SP Lower-Limit to SP Upper-Limit
SP Lower-Limit
SP Upper-Limit
EU
Set Point during SP
Ramp
SP Lower-Limit to SP Upper-Limit
PV
Temperature
Senor setting range Lower-Limit to
sensor setting range Upper-Limit
Sensor Setting
Range Lower-Limit
Sensor Setting
Range Upper-Limit
Analog
Analog scaling Lower-Limit to analog
scaling Upper-Limit
Scaling Lower-Limit
Scaling Upper-Limit
MV Monitor
(heating)
Standard
−5.0…105.0
0.0
100.0
%
Heating/cooling
0.0…105.0
MV Monitor
(cooling)
0.0…105.0
Table 5.BW
Analog Output Selection Types
Default
4-20: 4…20 mA
0-20: 0…20 mA
4-20
o1-t