Summary of alarm operations, Alarm latch – Rockwell Automation 900-TC32 Digital Temperature Controllers, Series B User Manual

Page 145

Advertising
background image

Publication 900-UM007D-EN-E - January 2011

Parameter Adjustments & Application Considerations

4-9

Alarm Latch

Alarm latch is a function where you can configure the alarm output once
turned ON to stay ON regardless of the process temperature.

The alarm latch function can be canceled by:

1. Turning the controller power OFF. Note, however, that it can also be

canceled by switching to the Initial Setting function group,
Communications Setting function group, Advanced Setting function
group, or Calibration function group.

2. Use the PF key (900-TC8).

3. Use an event input (900-TC8 and 900-TC16).

Summary of Alarm
Operations

The following figure summarizes the operation of alarms when the Alarm
Type parameter is set to “lower-limit alarm with standby sequence” and “close
in alarm” is set.

Figure 4.16 — Operation of Alarms Summary

Table 4.A

Symbol

Parameter: Group

Description

alh✽

Alarm 1 to 3 Hysteresis:
Initial Setting function
group

Alarm

rest

Standby Sequence:
Advanced Setting
function group

Alarm

✽ = 1 to 3

OFF

ON

PV

Alarm type: Lower-limit alarm with standby sequence

Alarm value

Alarm hysteresis

Time

Standby sequence
canceled

Alarm

Output

OFF (open)

ON (closed)