Temperature input shift – Rockwell Automation 900-TC32 Digital Temperature Controllers, Series B User Manual

Page 262

Advertising
background image

Publication 900-UM007D-EN-E - January 2011

5-34

Parameter Functions & Definitions

Related Parameter

• PV/SP (Operation function group, page 5-8), Input Type (Initial Setting

function group) (page 5-50)

Refer to the Advanced Setting function group:

• Event Input Assignment 1 (page 5-66)
• Event Input Assignment 2 (page 5-66)
• Number of Multi-SP Uses (page 5-65)
• Multi-SP Uses (page 5-71)

Temperature Input Shift

Conditions of Use:

The Input Type parameter must be configured as a

temperature (thermocouple or RTD) input (this excludes a non-contact
temperature sensor). The Input Shift Type parameter must be configured for
One-Point Shift.

Function:

Sometimes an error may exist between the measured temperature

(PV) and the actual temperature at the control target. To offset this error, add
your configured input shift value to the input (PV). The result is displayed on
the controller as the new measurement value (PV) and used for control.

Note:

The entire input range is shifted by the input shift value (1-point shift).
If the input shift value is set to –1

°C, the process is controlled to a value

obtained by subtracting 1

°C from the actual temperature (refer to

Figure 4.2).

Related Parameter

• Input Type (Initial Setting function group, page 5-50)
• Input Shift Type (Advanced Setting function group, page 5-86)

Table 5.AK Input Shift

Configurable Range

Units

Default Value

–199.9…+999.9

°C or °F

0.0

ins

Advertising