In-t – Rockwell Automation 900-TC32 Digital Temperature Controllers, Series B User Manual
Page 214

Publication 900-UM007D-EN-E - January 2011
4-78
Parameter Adjustments & Application Considerations
Operating Procedure
This procedure sets the Extraction of Square Root Low-cut Point parameter to
10.0%
Figure 4.170 — Operation function group
1. Press the
O Key for at least three seconds to move from the Operation to
the Initial Setting function group.
Figure 4.171
2. Press the
M Key to select the Extraction of Square Root Enable parameter.
Figure 4.172
3. Use the
U Key to select ON.
Figure 4.173
Table 4.AJ
Parameter Name
Configurable Range
Unit
Default
Extraction of the Square Root Enable
OFF: Disabled, ON: Enabled
---
OFF
Extraction of Square Root Low-cut Point
0.0...100
%
0.0
C
25
100
PV/SP
in-t
0
Input Type
sqr
off
Extraction
of Square
Root Enable
sqr
on
Extraction
of Square
Root Enable