Publication 900-UM007D-EN-E - January 2011

4-78

Parameter Adjustments & Application Considerations

Operating Procedure

This procedure sets the Extraction of Square Root Low-cut Point parameter to
10.0%

Figure 4.170 — Operation function group

1. Press the

O Key for at least three seconds to move from the Operation to

the Initial Setting function group.

Figure 4.171

2. Press the

M Key to select the Extraction of Square Root Enable parameter.

Figure 4.172

3. Use the

U Key to select ON.

Figure 4.173

Table 4.AJ

Parameter Name

Configurable Range

Unit

Default

Extraction of the Square Root Enable

OFF: Disabled, ON: Enabled

---

OFF

Extraction of Square Root Low-cut Point

0.0...100

%

0.0

C

25

100

PV/SP

in-t

0

Input Type

sqr

off

Extraction
of Square
Root Enable

sqr

on

Extraction
of Square
Root Enable