Parameter Functions & Definitions

5-55

PID ON/OFF

Function:

This parameter allows you to configure the controller for either the

2-PID control or ON/OFF control method.

The Auto-Tuning (AT) and Self-Tuning (ST) parameter functions can only be
used in the 2-PID control method.

Related Parameters

Refer to the Advanced Setting function group:

• AT Execute/Cancel (page 5-25), Manual Reset, Hysteresis heating,

Hysteresis cooling (page 5-38)

• ST Stable Range (page 5-75)

Standard or Heating/Cooling

Function:

This parameter allows you to configure the controller for the

standard control mode or heating and cooling control mode.

When using a 900-TC8X in the heating and cooling control mode, the
Auxiliary Output 3 terminal (SUB3) is typically (default) used for cooling
Control Output functions.

When using a 900-TC16X in the heating and cooling control mode, the
Auxiliary Output 2 output terminal (SUB2) is typically (default) used for
cooling Control Output functions.

When heating/cooling control is selected for the 900-TC32, the auxiliary
output 1 terminal (SUB1) is assigned as the controloutput (cooling).

Table 5.BL

Selections

Default Selection

pid: 2-PID

onof: ON/OFF

onof: ON/OFF

cntl

s-hc