In-t, Alt1, Amov – Rockwell Automation 900-TC32 Digital Temperature Controllers, Series B User Manual

Page 187

Advertising
background image

Publication 900-UM007D-EN-E - January 2011

Parameter Adjustments & Application Considerations

4-51

EXAMPLE

Operating Procedure: Loop Break Alarm Configurations

In this example, the LBA Detection Time is configured to 10, the LBA Level is
configured to 8.0, and the LBA Band is configured to 3.0.

Figure 4.96

1. Press the O key for at least 3 seconds to move from the Operation

function group to the Initial Setting function group.

Figure 4.97

2. Select the Alarm 1 Type parameter by pressing the M key.

Figure 4.98

3. Press the U key to configure the Alarm 1 Type parameter value to 12.

Figure 4.99

4. Select the Move to Advanced Setting function group parameter by

pressing the

M key.

Figure 4.100

C

25

100

PV/SP

in-t

5

Input type

alt1

2

Alarm 1 type

alt1

12

amov

0

Move to Advanced
Setting Function Group