Publication 900-UM007D-EN-E - January 2011

4-72

Parameter Adjustments & Application Considerations

7. Use the U key to set the parameter to 10. (The soak time unit is

configured in Soak Time Unit parameter in the Advance Setting
function group. The default is

m

(minutes).

Figure 4.159

8. Select the Wait Band parameter by pressing the M key.

Figure 4.160

9. Use the U key to set the parameter to 3.0.

Figure 4.161

10. Press the O key to move from the Adjustment function group to the

Operation function group.

Figure 4.162

soak

10

wt-b

off

Wait band

wt-b

3.0

C

25

100

PV/SP