Publication 900-UM007D-EN-E - January 2011

4-18

Parameter Adjustments & Application Considerations

• When using event inputs to switch the multi-SP, the event input

assignment display will not appear. Whether the set value and event
input assignments 1 and 2 will be displayed or hidden is shown in the
tables below.

• Do not connect the contacts from the same switch to more than one

900-TC Controller.

Two set points are set externally by using the Number of Multi-SP Uses
parameter

• Switching is possible between two set points (0 and 1) by setting the

Number of Multi-SP Uses parameter to 1. The default setting is 1 and
does not need to be changed to switch between two set points. Set
points 0 and 1 are specified by the status of event input 1.

Figure 4.32 — Event Inputs

When you want to configure event inputs to change the controllers four
pre-set Set points, you must properly configure the Number of Multi-SP Uses
parameter. Two set points (0 or 1) can be selected when the Number of
Multi-SP Uses parameter is set to 1 (default). This setting need not be changed.
Set point 0 or 1 is specified by the ON/OFF state of Event
Input 1.

Table 4.F

Number of
Multi-SP Uses Event Input Assignment 1

Event Input Assignment 2

0

Displayed (Multi-SP not used)

1

Hidden (Multi-SP, 2 Points).

Displayed (Event Input 2 not
used as Multi-SP Switch).

2

Hidden (Multi-SP, 4 Points).

A

EV2

EV2

EV1

EV1

+

+

900-TC16 Event Inputs

EV2

EV1

+

+

EV2

EV1

A

900-TC8 Event Inputs

DO NOT apply on external voltage source to the Event Input Terminals.