Heater Overcurrent Alarm
Set-up

To activate the heater overcurrent alarm (HOA), set the:

1.

Heater Overcurrent Use parameter to ON in the Advanced Setting
function group and

2.

Heater Overcurrent Detection 1 and Heater Overcurrent Detection 2
parameters in the Adjustment function group.

Note:

This procedure configures the Heater Overcurrent Detection 1
parameter to 20.0.

Moving to the Advanced Setting Function Group

The default setting for the Heater Overcurrent Use parameter is ON, so set
the Heater Overcurrent Detection 1 parameter

Move to the Advanced Setting function group. Press the

O

Key for at least three seconds to

move from the Operation to the Initial Setting function group.

Figure 3.125

3.

Press the

M Key to select the Move to Advanced Setting function

group parameter. (For details on moving between function groups, refer
to 4-8 Moving to the Advanced Setting function group.)

Figure 3.126

4.

Press the

D Key to enter the password (-169), and move from the

Initial Setting function group to the Advanced Setting function group.

Figure 3.127

The top parameter in the Advanced Setting function group is displayed.

C

25

100

PV/SP

in-t

5

Input Type

amov

-169

init

off

Move to the
Advanced
Setting
function group