Heater burnout alarm (hba) setup – Rockwell Automation 900-TC32 Digital Temperature Controllers, Series B User Manual

Page 125

Advertising
background image

Publication 900-UM007D-EN-E - January 2011

Configuration & Basic Operation

3-55

Figure 3.106 — Heater Burnout Detection

Heater Burnout Alarm (HBA) Setup

To activate the Heater Burnout Alarm (HBA), configure:

1.

the Heater Burnout (HB) ON/OFF parameter to ON in the Advanced
Setting function group, and

2.

the Heater Burnout Detection 1 and Heater Burnout Detection 2
parameters in the Adjustment function group.

EXAMPLE

Operating Procedure: Moving to the Advanced Setting Function Group

In this example configure the Heater Burnout Detection 1 parameter to 2.5.

The Heater Burnout Detection parameter setting is already ON by default, so
set the Heater Burnout Detection 1 parameter.

CT

CT

Load

200 V

10 A

10 A

200 V

200 V

Load

CT

CT

Load

200 V

5 A

5 A

200 V

200 V

Load

Burnout

To CT input

To CT input

Current when there is a burnout = 10 A

×

(1/2) = 5 A

Burnout

Current when there is a burnout = 0 A

To CT Controller input

To CT Controller input