1.

Move to the Advanced Setting function group.
Press the

O

key for at least 3 seconds to move from the Operation

function group to the Initial Setting function group.

Figure 3.107

2.

Select Move to Advanced Setting function group by pressing the

M key.

Figure 3.108

3.

Press the

D key to enter the password (−169), and move from the

Initial Setting function group to the Advanced Setting function group.
The top parameter in the Advanced Setting function group is displayed.

Figure 3.109

4.

Select the Heater Burnout Detection parameter by pressing the

M key.

Check that this parameter is set to ON (the default).
Next, set the Heater Current 1 Value Monitor parameter.

Figure 3.110