Parameter Adjustments & Application Considerations

EXAMPLE

Operation Procedure: Operation Function Group

In this example, apply a 1

°C by 1-shift to the input value of a type K

thermocouple sensor.

1. Press the

O

key to move from the Operation function group to the

Adjustment function group.

Figure 4.3 — Operation Function Group

Figure 4.4 Adjustment Function Group

2. Select the Temperature Input Shift parameter by pressing the

M

key.

Figure 4.5 — Temperature Input Shift

3. Press the

U

or

D

key to set 1.

Figure 4.6 — Set Shift Parameter

4. To return to the Operation function group, press the

O

key. The

process value is 1

°C larger than before the shift was applied.

Figure 4.7 — Operation Function Group

Note: The newly configured value or parameter is loaded into controller

memory if you do NOT operate any key on the front panel for at least
2 seconds or by pressing the

O

or

M

key.