L.adj – Rockwell Automation 900-TC32 Digital Temperature Controllers, Series B User Manual
Page 138

Publication 900-UM007D-EN-E - January 2011
4-2
Parameter Adjustments & Application Considerations
EXAMPLE
Operation Procedure: Operation Function Group
In this example, apply a 1
°C by 1-shift to the input value of a type K
thermocouple sensor.
1. Press the
O
key to move from the Operation function group to the
Adjustment function group.
Figure 4.3 — Operation Function Group
Figure 4.4 Adjustment Function Group
2. Select the Temperature Input Shift parameter by pressing the
M
key.
Figure 4.5 — Temperature Input Shift
3. Press the
U
or
D
key to set 1.
Figure 4.6 — Set Shift Parameter
4. To return to the Operation function group, press the
O
key. The
process value is 1
°C larger than before the shift was applied.
Figure 4.7 — Operation Function Group
Note: The newly configured value or parameter is loaded into controller
memory if you do NOT operate any key on the front panel for at least
2 seconds or by pressing the
O
or
M
key.
C
30
200
l.adj
Adjustment level
display
C
ins
0.0
Temperature
input shift
C
ins
1.0
C
31
200