Parameter Adjustments & Application Considerations
4-17
Setting Event Input
• Event inputs can be used for Multi-SP, RUN/STOP, Auto/Manual
Switch, Program Start, Invert Direct/Reverse Operation, 100% AT
Execute/Cancel, 40% AT Execute/Cancel, Setting Change
Enable/Disable, and Alarm Latch Cancel.
• Of these, only the number of event inputs (0 to 2) set in the Number of
Multi-SP Uses parameter (Initial Setting function group) are used for the
multi-SP function.
• Event inputs (1 and 2) that are not used for the multi-SP function are
assigned using the Event Input Assignment (1 and 2) parameters (Initial
Setting function group).