Rockwell Automation 900-TC32 Digital Temperature Controllers, Series B User Manual

Page 158

Advertising
background image

Publication 900-UM007D-EN-E - January 2011

4-22

Parameter Adjustments & Application Considerations

Figure 4.39 —Event Inputs

Operation Commands Other than Multi-SP

The following table shows the functions assigned when an Event Input
Assignment (1 or 2) is displayed.

Note (1) PRST (Program Start) can be set even when the Program Pattern parameter is set to OFF, but the function

will be disabled.

(2) This function can be set for heating/cooling control, but the function will be disabled.

When any of the following functions are set for an Event Input Assignment
parameter, the same function cannot be set for another Event Input
Assignment parameter: STOP (RUN/STOP), MANU (Auto/Manual Switch),
PRST (Program Start), DRS (Invert Direct/Reverse Operation), AT-2 (100%
AT Execute/Cancel), AT-1 (40% AT Execute/Cancel), WTPT (Setting
Change Enable/Disable), or LAT (Alarm Latch Cancel). Turn event inputs
ON and OFF while the power is being supplied. Event input ON/OFF
changes are detected for inputs of 50 ms or longer. (However, inputs of 250
ms or longer is determined using logic operations.)

The functions are described in detail below. Event inputs 1 and 2 are taken as
examples.

Table 4.J — When Event Input Assignment (1 or 2) is Displayed

Setting

Function

none

None

stop R

RUN/STOP

manu

Auto/Manual

prst

Program Start (See note 1.)

drs

Invert Direct/Reverse Operation

at-2

100% AT Execute/Cancel

at-1

40% AT Execute/Cancel (See note 2.)

wtpt

Setting Change Enable/Disable

lat

Alarm Latch Cancel

EV2

EV2

EV1

EV1

+
+

EV2

EV1

EV2

EV1

+

+

900-TC16

900-TC8

Note: Do not apply an external voltage source to the Event Input Terminals.