Sl-h sl-l, Set point upper-limit, set point lower-limit – Rockwell Automation 900-TC32 Digital Temperature Controllers, Series B User Manual

Page 282

Advertising
background image

Publication 900-UM007D-EN-E - January 2011

5-54

Parameter Functions & Definitions

Set Point Upper-Limit,

Set Point Lower-Limit

Function:

These parameters allow you to configure the maximum allowable

range for an operator to enter the set point value. The SP can be configured
within the range defined by the Upper- and Lower-Limit values in the Set
Point Upper-Limit and Set Point Lower-Limit parameters. If an attempt is
made to enter a SP value outside the upper or Lower-Limit from the keypad
the set point display will flash at the configured maximum upper- or
Lower-Limit value.

If the temperature Input Type or temperature units are changed, the set point
Upper-Limit and set point Lower-Limit are forcibly changed by the controller
to the default Upper- and Lower-Limits of the newly configured sensor.

For a temperature input, the decimal point position is dependent on the
currently selected sensor. For an analog input, it is dependent on the Decimal
Point parameter setting.

Related Parameters

• Input Type (page 5-50), Temperature Units (°C/°F) Selection (page

5-53) (Initial Setting function group)

Table 5.BJ — Controllers with Thermocouple/Resistance Thermometer Inputs

Parameter

Input Type

Configurable Range

Units

Default

Set Point
Upper-Limit

Temperature

SP Lower-Limit + 1 to Input
range Upper-Limit

EU

1300

Millivolt

SP Lower-Limit + 1 to scaling
Upper-Limit

EU

100

Set Point
Lower-Limit

Temperature

Input range Lower-Limit to SP
Upper-Limit

− 1

EU

−200

Millivolt

Scaling Lower-Limit to SP
Upper-Limit

− 1

EU

0

Table 5.BK — Controllers with Analog Inputs (900-TC8 & 900-TC16)

Parameter

Configurable Range

Units

Default

Set Point Upper-Limit

SP Lower-Limit + 1 to scaling
Upper-Limit

EU

100

Set Point Lower-Limit

Scaling Lower-Limit to SP
Upper-Limit

− 1

EU

0

sl-h
sl-l

Advertising