Parameter Adjustments & Application Considerations

4-49

Parameters Related to Loop Break Alarms

➊ Set NONE as the unit for analog inputs.

• A loop break alarm can be output by setting the Alarm 1 Type to 12

(LBA).

• A setting of 12 (LBA) can be configured for Alarm 2 or 3 but the setting

will be disabled.

• Loop breaks are not detected during SP Ramp operation.

• Loop breaks are not detected during Auto-Tuning, Manual operation, or

while the controller is stopped.

• If the Alarm 1 Latch parameter is configured to ON, the latch will be

effective for the loop break alarm.

Automatically Setting the LBA Detection Time

• The LBA Detection Time is automatically configured by Auto-Tuning.

(However, it is not configured automatically for heating/cooling
control.)

• If the optimum LBA Detection Time is NOT obtained by Auto-Tuning,

configure the LBA Detection Time parameter (Advance Setting
function group).

Table 4.AB

Parameter Name

Symbol

Sensor Type

Configurable Range
(Units)

Application
Considerations

LBA Detection Time

lba

0…9999 (s)

Setting 0 disables the LBA
function.

LBA Level

lbal

Controllers with
Thermocouple and
Resistance Thermometer
(RTD) inputs

0.1…999.9 (

°C/°F) ➊

Default: 8.0 (

°C/°F)

Controllers with Analog
Inputs

0.01…99.99 (%FS)

Default: 10.00% FS

LBA Band

lbab

Controllers with
Thermocouple and
Resistance Thermometer
(RTD) inputs

0.0…999.9 (

°C/°F) ➊

Default: 3.0 (

°C/°F)

Controllers with Analog
Inputs

0.00…99.99 (%FS)

Default: 0.20% FS