Using the simple program function, Simple program function – Rockwell Automation 900-TC32 Digital Temperature Controllers, Series B User Manual
Page 202

Publication 900-UM007D-EN-E - January 2011
4-66
Parameter Adjustments & Application Considerations
Using the Simple Program
Function
Simple Program Function
The simple program function can be used to perform a simple one step ramp
and soak operation.
Figure 4.146
The simple program will start when the Program Start parameter is changed
from RSET to STRT. END will be displayed on the No. 2 display and the
output assigned as the program end output will turn ON after the time
configured in the Soak Time parameter has expired in the wait band. The
Program Pattern parameter can be used to select moving to STOP mode or
continuing operation in RUN mode after the program ends.
➊ The configurable units for the Wait Band parameter is %FS for Controllers with Analog Inputs and the range is
OFF or 0.01…99.99.
➋ Units configured for Controllers with Thermocouple/Resistance Thermometer Multi-inputs. Set NONE as the
unit for Controllers with Analog Inputs.
RSET
→
STRT
PV
SP
Set point
Wait band
Wait band
Soak time
END display
END output
Select either
STOP or RUN.
Table 4.AF —Parameters Related to the Simple Program Function
Parameter Name
Symbol
Configurable (Monitor) Values
Units
Display Function
Group
Program Pattern
ptrn
OFF, STOP, CONT
—
Initial Setting
Program Start
prst
RSET, STRT
—
Operation
Soak Time
soak
1…9999
min or h
Adjustment
Soak Time Unit
t-u
m (minutes)/h (hours)
—
Advanced Setting
Wait Band
wt-b
OFF or 0.1…999.9
➊
°C or °F ➊ ➋
Adjustment
Soak Time Remain Monitor
sktr
0…9999
min or h
Operation