Publication 900-UM007D-EN-E - January 2011

4-42

Parameter Adjustments & Application Considerations

Setting

Configuring the PV Color Change to Indicate Stable Status

To display the PV as a constant green color (to indicated a stable condition)
display when the PV is within

±15.0°C of the set point, configure the PV

Color Change and PV Stable Band parameters.

PV Color Change =

r-gr (Red to Green to Red)

PV Stable Band = 15.0

°C

EXAMPLE

Operating Procedure

Note: Make sure you release the protection to Move to the Advanced Setting

function group before you configure the PV Color Change and PV
Stable Band parameters since both parameters are located in the
Advanced Setting function group. (Refer to steps 1…8 on page 4-31.)

Figure 4.74

1. Press the O key for at least 3 seconds to move from the Operation

function group to the Initial Setting function group.

Figure 4.75

2. Select the Move to Advanced Setting function group parameter by

pressing the

M key.

Figure 4.76

C

25

100

PV/SP

in-t

5

Input type

amov

-169

Move to advanced function setting level